Conductor:bare
copper, tinned copper
Insulator: silicone rubber
Jacket: Silicone rubber
Rated Volt.:600/1000V
Test Voltage: 3000V. 5Min
Rated Temp.:-60℃~+180℃
Mechanical properties:
Tensile strength: ≥5N/mm2
Elongation at break of insulation: ≥150%
Silicone rubber wire & cable have very good flexibility and
good performance of resistance to high temperature, range from -55℃ up to
180℃.
The use of silicone rubber, a high grade corona resistant
insulation material, gives the cable excellent dielectric strength.
Application:
Silicone wire & cable are used where high flexibility is
required and high temperature conditions. It is therefore a suitable connection
cable for home electric appliance, high voltage machines like transformers,
generators, motors, traction machines.
Core×Cross
Section
|
Structure
|
Insulation
|
Jacket
|
Cable OD
|
20℃ Max
Resist. Ω/KM
|
Thick
|
OD
|
Nominal
|
Toler.
|
mm2
|
No./Dia. mm
|
mm
|
mm
|
mm
|
mm
|
mm
|
Bare
|
Tinned
|
3×4
|
56/0.30
|
0.8
|
4.3
|
1.8
|
16.5×7.9
|
±0.50
|
4.95
|
5.09
|
3×6
|
84/0.30
|
0.8
|
4.9
|
2.0
|
18.7×8.9
|
±0.50
|
3.30
|
3.39
|
3×10
|
84/0.40
|
1.0
|
6.6
|
2.5
|
24.8×11.6
|
±0.60
|
1.91
|
1.95
|
3×16
|
126/0.40
|
1.2
|
8.2
|
2.8
|
30.2×13.8
|
±0.80
|
1.21
|
1.24
|
3×25
|
196/0.40
|
1.4
|
10.1
|
3.0
|
36.3×16.1
|
±0.80
|
0.78
|
0.795
|
3×35
|
276/0.40
|
1.4
|
11.4
|
3.2
|
40.6×17.8
|
±1.0
|
0.554
|
0.565
|
3×50
|
396/0.40
|
1.6
|
13.9
|
3.5
|
48.7×20.9
|
±1.0
|
0.386
|
0.393
|
3×70
|
360/0.50
|
1.6
|
15.6
|
3.8
|
54.4×23.2
|
±1.0
|
0.272
|
0.277
|
3×95
|
475/0.50
|
1.8
|
18.1
|
4.0
|
62.3×26.1
|
±1.2
|
0.206
|
0.210
|
3×120
|
608/0.50
|
2.0
|
20.0
|
4.5
|
69×29
|
±1.5
|
0.161
|
0.164
|
3×150
|
756/0.50
|
2.2
|
22.4
|
4.8
|
76.8×32
|
±1.5
|
0.129
|
0.132
|
3×185
|
925/0.50
|
2.4
|
24.8
|
5.2
|
84.8×35.2
|
±2.0
|
0.106
|
0.108
|
3×240
|
1221/0.50
|
2.6
|
28.2
|
5.5
|
95.6×39.2
|
±2.0
|
0.0801
|
0.082
|
|