Conductor£ºbare
copper, tinned copper
Insulator: silicone rubber
Rated Volt.£º 600V
Test Voltage: 2000V. 1Min
Rated Temp.£º-60¡æ¡«+150¡æ
Mechanical properties
Un-aged condition:
Tensile strength: 3.45N/mm2 min.
Elongation at break of insulation: ¡Ý100%
Min.Bending radius: 6¡ÁOD
Standards: Standard: UL758,
UL62, And UL1581
Meet with RoHS,
REACH rules.
Characteristics:
Silicone rubber wire & cable have very good flexibility and
good performance of resistance to high temperature, range from -55¡æ up to 150¡æ.
The use of silicone rubber, a high grade corona resistant
insulation material, gives the cable excellent dielectric strength.
Application:
Silicone wire & cable are used where high flexibility is
required and high temperature conditions. It is therefore a suitable connection
cable for home electric appliance, high voltage machines like transformers,
generators, motors, traction machines.
AWG
|
Conductor
|
Insulation
|
Wire OD
|
Resis.
|
Size
|
Structure
|
OD
|
Nominal
|
Nominal
|
Tolerance
|
¦¸/KM
|
NO.
|
mm2
|
No./mm
|
mm
|
mm
|
mm
|
mm
|
Max.
|
26
|
0.128
|
7/0.16
|
0.48
|
1.14
|
2.80
|
¡À0.15
|
148
|
24
|
0.205
|
7/0.20
|
0.60
|
1.14
|
2.90
|
¡À0.15
|
93
|
22
|
0.324
|
7/0.25
|
0.75
|
1.14
|
3.05
|
¡À0.20
|
55
|
20
|
0.519
|
7/0.31
|
0.93
|
1.14
|
3.25
|
¡À0.20
|
34.6
|
18
|
0.823
|
7/0.39
|
1.17
|
1.14
|
3.45
|
¡À0.30
|
23.2
|
16
|
1.31
|
7/0.49
|
1.47
|
1.14
|
3.75
|
¡À0.30
|
14.6
|
14
|
2.08
|
41/0.254
|
1.86
|
1.14
|
4.15
|
¡À0.30
|
8.96
|
12
|
3.31
|
43/0.32
|
2.50
|
1.14
|
4.80
|
¡À0.30
|
5.64
|
10
|
5.261
|
35/0.45
|
3.20
|
1.14
|
5.50
|
¡À0.30
|
3.55
|
|